SKM Air Conditioning Testing Laboratory

Initial Accreditation Date:Dec 14 , 2016

معلومات الاتصال

العنوان

Sharjah, United Arab Emirates

صندوق بريد / الرمز البريدي

6004

البريد الإلكتروني

lab@skmaircon.com

الموقع الإلكتروني

www.skmaircon.com

المجال الرئيسي

Testing Laboratories

ساري منذ:Jul 11 , 2023

Type of Activity Test Materials / Products Test Name Test Method Status
Performance Testing of Electric
  • Physical and Mechanical
  • Ducted Air Conditioners
  • Dry Bulb Temperature of Air Leaving Equipment:[-8 °C - 60 °C]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Wet Bulb Temperature of Air Leaving Equipment: [-8 °C - 60 °C]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Wet Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Entering Water Temperature: [-8 °C - 60 °C]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Leaving Water Temperature: [-8 °C - 60 °C]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Water Flow Rate: [1 GPM - 50 GPM]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Water Pressure Drop: [0 inH2O – 350 inH2O]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Outdoor Dry Bulb Temperature: [-8 °C - 60 °C]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Volume Flow Rate of Air: [200 CFM - 10000 CFM]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Power Input To Equipment : [0 kW - 30 kW]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Static Pressure: [0 inH2O - 5 inH2O]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Barometric Pressure: [80kPA - 120kPA]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Cooling Capacity: [0.5 TR - 10 TR]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Energy Efficiency %[Derived From Calculations]
ISO 13253 SASO 2682 SASO 2663:2021 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358/Amd 1 SASO 2874 UAE.S5010-5 UAE.S5010-1 AHRI 210/240 AHRI 340/360 ASHRAE-37 ASHRAE-79 AHRI 440 AHRI 1360 AHRI 1230 ASHRAE 127 IEC 60335-2 40 IEC 60335-1 ,AMD1:2013 AMD2:2016Active
  • Non-Ducted Air Conditioners
  • Dry Bulb Temperature of Air Leaving Equipment:[-8 °C - 60 °C]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Wet Bulb Temperature of Air Leaving Equipment: [-8 °C - 60 °C]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Wet Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Entering Water Temperature: [-8 °C - 60 °C]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Leaving Water Temperature: [-8 °C - 60 °C]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Water Flow Rate: [1 GPM - 40 GPM]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Water Pressure Drop: [0 inH2O – 350 inH2O]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Outdoor Dry Bulb Temperature: [-8 °C - 60 °C]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Volume Flow Rate of Air: [200 CFM - 10000 CFM]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Power Input To Equipment : [0 kW - 30 kW]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Static Pressure: [0 inH2O - 5 inH2O]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Barometric Pressure: [80kPA - 120kPA]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Cooling Capacity: [0.5TR - 6TR]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Energy Efficiency %[Derived From Calculations]
SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 ISO 5151 SASO 2874 SASO 2681 UAE.S ISO 5151 UAE.S5010-5 UAE.S5010-1 AHRI 440 ASHRAE-79 ASHRAE-37 AHRI 1230 AHRI 1360 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Packaged Air Conditioner
  • Measurement Range of Dry Bulb Temperature of Air Leaving Equipment: [-8 °C - 60 °C]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Measurement Range of Wet Bulb Temperature of Air Leaving Equipment: [-8 °C - 60 °C]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Measurement Range of Dry Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Measurement Range of Wet Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Measurement Range of Outdoor Dry Bulb Temperature: [-8 °C - 60 °C]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Measurement Range of Volume Flow Rate of Air and All Relevant for its Calculations: [1000 CFM - 20,000 CFM]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Measurement Range of Power Input To Equipment: [5 kW - 720 kW]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Measurement Range of Barometric Pressure: [321 inH2O - 642.34 inH2O]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Measurement Range of Static Pressure: [0 inH2O - 4 inH2O]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Measurement Range of Cooling Capacity: [6 TR - 40 TR]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Energy Efficiency %[Derived From Calculations]
ISO 13253 UAE.S5010-5 UAE.S5010-1 ASHRAE-37 SASO 2682 SASO 2874 SASO 2663 SASO ISO 16358-1 ISO 16358-1/Cor 1 ISO 16358-1/Amd 1 AHRI 340/360 AHRI 210/240 AHRI 1360 AMCA 210 ASHRAE 127 IEC 60335 2 40 IEC 60335 1 ,AMD1:2013 AMD2:2016Active
  • Air Handling Units
  • Entering Water Temperature: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Leaving Water Temperature: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Water Flow Rate: [1 GPM - 100 GPM]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Water Pressure Drop: [0 inH2O – 350 inH2O]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Dry Bulb Temperature of Air Leaving Equipment: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Wet Bulb Temperature of Air Leaving Equipment: [-8°C - 60°C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Dry Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Wet Bulb Temperature of Air Entering Equipment: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Outdoor Dry Bulb Temperature: [-8 °C - 60 °C]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Volume Flow Rate of Air and All Relevant for its Calculations: [1000 CFM - 20,000 CFM]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Power Input To Equipment: [5 kW - 720 kW]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Barometric Pressure: [321 inH2O - 642.34 inH2O]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Static Pressure: [0 inH2O - 4 inH2O]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Measurement Range of Cooling Capacity: [6 TR - 40 TR]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Energy Efficiency %[Derived From Calculations]
DIN EN 1886 EN 13053 AHRI 430 AHRI 1350 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Air Cooled Packaged Chillers
  • Entering Water Temperature: [0°C - 60°C]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Leaving Water Temperature: [0 °C - 60 °C]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Condenser Entering Temperature: [0 °C - 60 °C]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Water Flow Rate: [41 GPM - 1200 GPM]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Water Pressure Drop: [0 inH2O – 642 inH2O]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Power Input To Equipment: [5 kW - 720 kW]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Cooling Capacity: [4 TR - 410 TR]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active
  • Energy Efficiency %[Derived From Calculations]
AHRI 550/590 AHRI 551/591 IEC 60335 2 40 IEC 60335 1 AMD1:2013 AMD2:2016Active